| Scanning method |
Thru scan |
Thru scan
(with light quantity
adjustment
potentiometer) |
Polarized
retroreflective |
Polarized
retroreflective
(with light quantity
adjustment
potentiometer) |
Diffuse scan |
Diffuse scan
(wide beam area) |
| Catalog listing |
HPB-T1
HPB-T2 |
HPB-T3
HPB-T4 |
HPB-P1
HPB-P2 |
HPB-P3
HPB-P4 |
HPB-A1
HPB-A2 |
HPB-D1
HPB-D2 |
| Supply voltage |
10 to 30Vdc |
| Current consumption |
55mA max. Emitter: 30mA
Receiver:25mA |
30mA max. |
30mA max. |
| Scanning distance |
10m |
2.5m (when reflector FE-RR8 is used) |
0.5m |
50mm |
| Detection object |
Opaque object 9mm dia. min. |
Opaque object 80mm dia. min.
(when reflector FE-RR8 is used) |
- |
| Standard target object |
- |
- |
20 x 20cm white paper |
10 x 10cm white paper |
| Scanning angle |
2 to 20° |
Body: 1 to 10°, reflector: 40°min. |
- |
| Differential travel |
- |
- |
20% max.
(within rated sensing distance) |
| Operation mode |
Set operation mode selection line.
Operation mode selection line open or 0V connection: light ON/Vcc connection: dark ON |
| Output mode |
Output mode HPB- 1, HPB- 3: NPN transistor output, open collector
HPB- 2, HPB- 4: PNP transistor output, open collector |
| Control output |
Switching current: 100mA max. (resistive load)
Output dielectric strength: 30V
Voltage drop: 2V max. (at 100mA switching circuit) |
| Response time |
1ms max. (for operation and recovery) |
| Light emitter |
Infrared LED |
Red LED |
Infrared LED |
| Indicator lamps |
Other than thru scan emitter: output ON indicator (orange), stability indicator (green), Thru scan emitter: power indicator (orange) |
Ambient light immunity
(at light receiving surface) |
Incandescent lamp 5,000lx max., sunlight 20,000lx max. |
| Operating temperature range |
-25 to +60°C (non-freezing, non-condensing) |
| Operating humidity range |
35 to 85%RH (non-freezing, non-condensing) |
| Storage temperature range |
-40 to +70°C (non-freezing, non-condensing) |
| Insulation resistance |
20M min. (by 500Vdc megger) |
| Vibration resistance |
10 to 55Hz, 1.5mm peak-to peak amplitude, 2hrs in X, Y and Z directions |
| Shock resistance |
500m/s2 10 times in X, Y and Z directions |
| Protection |
IP67 (IEC standard) |
| Wiring method |
Pre-leaded |
| Weight |
Approx. 60g (body only, with 2m cord) |
| Circuit protection |
Reverse connection protection circuit, output short-circuit protection circuit, power ON malfunction prevention circuit (approx. 50ms) |